The e.temperature interface has 16x PT1000 inputs for measuring temperatures.
The e.temperature interface communicates with other devices via an I²C interface.
This makes it the ideal addition to the e.manager nD2, mc2 and the SmartPi.
Compatible with:
e.manager nD
e.manager mc
SmartPi


Technical data:
|
Input voltage: |
5V DC |
|
Input current: |
< 50 mA |
|
Connection: |
Screw terminals |
|
Temperature inputs: |
PT1000 : 16x |
|
Driver voltage: |
12V DC |
|
Weight: |
200 g |
|
Operating temperature: |
- 10 to + 50°C |
|
Protection rating: |
IP 10 |
|
Dimensions: |
158 x 90 x 58 mm (WxHxD) |
I²C ADDRESS setting

Terminal designation
| Terminal designation |
T1 + /_ |
T2 + /_ |
T3 + /_ |
T4 + /_ |
T5 + /_ |
T6 + /_ |
T7 + /_ |
T8 + /_ |
T9 + /_ |
T10 + /_ |
T11 + /_ |
T12 + /_ |
T13 + /_ |
T14 + /_ |
T15 + /_ |
T16 + /_ |
Bytes | Data type | Factor | Value range |
Byte Order |
|||||||
| Register | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 | 4 Bytes | FLOAT | IEEE-754 | HIGH _> LOW | ||||||||
| Register | 17 | 18 | 19 | 20 | 21 | 22 | 23 | 24 | 25 | 26 | 27 | 28 | 29 | 30 | 31 | 32 | 4 Bytes | signed long int | Factor 100 | -21,474,836.48°C to 21,474,836.47°C | Big Endian | |||||||
| Register | 33 | 34 | 35 | 36 | 37 | 38 | 39 | 40 | 41 | 42 | 43 | 44 | 45 | 46 | 47 | 48 | 2 Bytes | signed int | Factor 100 | -327.68°C to +327.67°C | Big Endian | |||||||
| Register | 200 | Calibrate with 1.15 kOhm | ||||||||||||||||||||||||||
| Register | 250 | Version | ||||||||||||||||||||||||||
| Register | 255 | Restart | ||||||||||||||||||||||||||
Pin assignment of the connection socket