RS485
30 devices per bus, max. 100 devices
Power reduction
RS485
Connect the inverters to each other using a patch cable.
Cut open the cable from the last inverter to the e.manager and connect the individual wires to the e.manager as follows.
e.manager terminal A <=> PIN 3 (yellow-white)
e.manager terminal B <=> PIN 6 (yellow)
Alternatively via the terminal block
e.manager terminal A <=> PIN 2 RX/TX B(+)
e.manager terminal B <=> PIN 3 RX/TX A(-)
No settings are required for UniLynx inverters.
Password
Enter the password 1761. The display shows “Security level: 1”
Setup
Security
No settings are required for UniLynx inverters.
Device address
For the address, enter a unique address between 1 and 32. Set the network and subnet to 1.
- Network: 1
- Subnet: 1
- Address: X
Setup
Communication setup
ComLynx setup
After each change, restart the inverter on both the AC and DC side.