RS485

PowerOne ABB

RS485 connection

Connection diagram PowerOne ABB
Connection diagram PowerOne ABB

Connect the inverters to each other with a patch cable.

Disconnect the cable from the last inverter to the e.manager and connect the individual lines to the e.manager as follows.

e.manager terminal A <=> PIN 3 (yellow-white)
e.manager terminal B <=> PIN 5 (yellow)

Plug view
Plug view

Inverter configuration

Please proceed as follows for each inverter.

Set device address

Press ESC key

Settings

Adress

Here please enter a unique address between 2 and 63.

The default password is: 0000

Go back