RS422
Fronius
Inverter types
IG-Plus and IG-TL
At Fronius, two RS485 inputs of the e.manager nD are used. Only the RS485-III interface can then still be used to connect other inverter manufacturers!
RS422 connection

Connect the inverters to each other with a patch cable. Make sure that you always connect OUT with IN.
At the last inverter, please connect wires 3 and 4, as well as wires 5 and 6 with each other.
Disconnect the cable from the last inverter to the e.manager and connect the individual wires to the e.manager as follows.
e.manager RS485 I Terminal A <=> PIN 3 (green-white)
e.manager RS485 I Terminal B <=> PIN 6 (green)
e.manager RS485 II Terminal A <=> PIN 4 (blue)
e.manager RS485 II Terminal B <=> PIN 5 (blue-white)

Optionally you can also connect a RS422 to RS485 converter in between. This converter can then ONLY be connected to RS485-II or RS485-III.
Inverter configuration
Please proceed as follows for each inverter.
Inverter number
Setup
Inverter number (IG-NR)
Here please enter a unique address between 1 and 99.
Protocol
Setup
DATCOM (MIXmode)
Protocoltype(MODE)
Please select the communication protocol "Interface" or IFP here.
Set baud rate
Is only necessary for IG Plus and CL devices
Setup
MIXmode
MODE
IFP
Please set 19200 baud here.
You may have to enter a numerical code for the IG Plus and CL devices so that you can change settings. The number code is: 22742
RS485 Modbus
Fronius
Inverter types
All, one inverter must have a data manager. Max. 10 inverters.
For Modbus use, a Datamager must be installed in a WR.
RS485 connection

Connect the inverters to each other with a patch cable. Make sure that you always connect OUT with IN.
At the last inverter, please connect wires 3 and 4, as well as wires 5 and 6 with each other.
Connect the data manager from the last inverter to the e.manager.
Inverter configuration
Leave all settings unchanged (protocol: Solarnet).
Connect to the Datamanager and activate the Modbus.
Data output via Modbus: rtu
Baudrate: 9600
Parität: keine
SunSpec Model Type: float
Inverter control via Modbus: aktiv
Modbus TCP via IP addresses
Fronius
With this variant, all inverters are addressed directly via an IP address.
Inverter types
Symo, Eco, Primo or an inverter with Datamanager.

Inverter configuration
Please proceed as follows for each inverter.
Call up the web page of the Fronius inverter.
RS422 ID
The RS422 ID must be set to 1.
IP Address
Assign a unique IP address to each inverter.
Communication settings
Datenausgabe über Modbus: tcp
Wechselrichter-Steuerung über Modbus: aktiv
JSON: aktiv
Modbus ID: 1
Modbus TCP über RS422
Fronius
In this variant, only one inverter is addressed directly via an IP address, the other inverters are then queried via RS422.
Inverter types
Symo, Eco, Primo, IG-PLus, IG-TL. An inverter must have a data manager.

Inverter configuration
Please proceed as follows for each inverter
RS422 ID
Assign a unique RS422 ID to each inverter. The IDs must start at 1 and be consecutive!!!
Leave all other settings at the default settings.
For the inverter with the data logger
IP address
Assign a unique IP address to the inverter.
Call up the Fronius inverter's website.
Communication settings
Data output via Modbus: tcp
Inverter control via Modbus: aktiv
JSON: aktiv
Modbus ID: 1