RS422

Fronius

Inverter types

IG-Plus and IG-TL

At Fronius, two RS485 inputs of the e.manager nD are used. Only the RS485-III interface can then still be used to connect other inverter manufacturers!

RS422 connection

Connection diagram Fronius
Connection diagram Fronius

Connect the inverters to each other with a patch cable. Make sure that you always connect OUT with IN.

At the last inverter, please connect wires 3 and 4, as well as wires 5 and 6 with each other.

Disconnect the cable from the last inverter to the e.manager  and connect the individual wires to the e.manager as follows.

e.manager RS485 I Terminal A <=> PIN 3 (green-white)
e.manager RS485 I Terminal B <=> PIN 6 (green)
e.manager RS485 II Terminal A <=> PIN 4 (blue)
e.manager RS485 II Terminal B <=> PIN 5 (blue-white)

Plug view
Plug view

Optionally you can also connect a RS422 to  RS485 converter in between. This converter can then ONLY be connected to RS485-II or RS485-III.

Inverter configuration

Please proceed as follows for each inverter.

Inverter number

Setup

Inverter number (IG-NR)

Here please enter a unique address between 1 and 99.

Protocol

Setup

DATCOM (MIXmode)

Protocoltype(MODE)

Please select the communication protocol "Interface" or IFP here.

Set baud rate

Is only necessary for IG Plus and CL devices

Setup

MIXmode

MODE

IFP

Please set 19200 baud here.

You may have to enter a numerical code for the IG Plus and CL devices so that you can change settings. The number code is: 22742

RS485 Modbus

Fronius

Inverter types

All, one inverter must have a data manager. Max. 10 inverters.

For Modbus use, a Datamager must be installed in a WR.

RS485 connection

Connection diagram Fronius Modbus
Connection diagram Fronius Modbus

Connect the inverters to each other with a patch cable. Make sure that you always connect OUT with IN.

At the last inverter, please connect wires 3 and 4, as well as wires 5 and 6 with each other.

Connect the data manager from the last inverter to the e.manager.

Inverter configuration

Leave all settings unchanged (protocol: Solarnet).

Connect to the Datamanager and activate the Modbus.

Data output via Modbus:               rtu

Baudrate:                               9600

Parität:                                keine

SunSpec Model Type:                     float

Inverter control via Modbus:   aktiv

Modbus TCP via IP addresses

Fronius

With this variant, all inverters are addressed directly via an IP address.

Inverter types

Symo, Eco, Primo or an inverter with Datamanager.

Connection diagram Fronius
Connection diagram Fronius

Inverter configuration

Please proceed as follows for each inverter.

Call up the web page of the Fronius inverter.

RS422 ID

The RS422 ID must be set to 1.

IP Address

Assign a unique IP address to each inverter.

Communication settings

Datenausgabe über Modbus:               tcp

Wechselrichter-Steuerung über Modbus:   aktiv

JSON:                                   aktiv

Modbus ID:                              1

Modbus TCP über RS422

Fronius

In this variant, only one inverter is addressed directly via an IP address, the other inverters are then queried via RS422.

Inverter types

Symo, Eco, Primo, IG-PLus, IG-TL. An inverter must have a data manager.

Connection diagram Fronius
Connection diagram Fronius

Inverter configuration

 

Please proceed as follows for each inverter

RS422 ID

Assign a unique RS422 ID to each inverter. The IDs must start at 1 and be consecutive!!!

Leave all other settings at the default settings.

 

For the inverter with the data logger

IP address

Assign a unique IP address to the inverter.

 

Call up the Fronius inverter's website.

Communication settings

Data output via Modbus:               tcp

Inverter control via Modbus:   aktiv

JSON:                                   aktiv

Modbus ID:                              1