RS485

Danfoss

RS485 connetion

connection diagram Danfoss
connection diagram Danfoss

Optionally, you can also connect the inverters to each other with a network cable.

e.manager terminal A <=> Danfoss WR terminal RX/TX B(+)
e.manager terminal B <=> Danfoss WR terminal RX/TX A(-)

Inverter configuration

UnixLynx inverters do not require any settings to be made.

Please proceed as follows for each inverter:

Password

Setup

Security

And enter the password 1761. The display shows "Security level: 1".

Inverter address

Setup

Communication-Setup

ComLynx-Setup

Please enter the following:

  • Network: 1
  • Subnet: 1
  • Address: X

Please enter a unique address here.

For TripleLynx inverters, the address must be between 1-50.

Restarting the inverter

To ensure that all parameters are safely adopted, please restart the inverter (switch off the voltage on the AC and DC sides for at least five minutes).